High Efficiency Air Cooled Screw Chiller Air Conditioner

Type: Central Air Conditioners
Usage: Room
Indoor Machine Noise: 36-49dB
Certification: CE
Cooling/Heating: Cooling/Heating
Power Source: Electrical
Customization:
Diamond Member Since 2017

Suppliers with verified business licenses

Manufacturer/Factory, Trading Company

Basic Info.

Power Type
AC
Condition
New
Refrigerant
R134A/R407c
Heat Exchanger
Shell and Tube
Transport Package
Plastic Film Wrapped
Trademark
AMRTA or OEM
Origin
China
HS Code
8418612090

Product Description

The compressor

The unit is equiped with semi-hermetic screw compressor, compared with the piston compressor, semi-hermetic screw compressor has two advantages:

Less parts(About 1/3 of the piston compressor), simple structure, less wearing parts, high reliability and long life;

Compressor suction and exhaust uniform, exhaust temperature is low, vibration is small, not sensitive to wet compression, anti-liquid strike ability.

Tube-fin air-cooled condenser

The tube-fin air-cooled condenser adopts the inverted "V" type layout, on the one hand, it improves the space utilization ratio, increases the heat exchange area, on the other hand, it improves the airflow and heat transfer efficiency, so that improve the unit's cooling and heating capacity.

Throttling equipment

For expansion valve, we select the most advanced products, with a compact overall design, rugged stainless steel diaphragm, and in a wide range of operating conditions to provide stable and accurate control.

Tube-shell evaporator

Using shell and tube structure, the outside is proceeded with fire-retardant,waterproof insulation materials, water side of the working pressure is 1.0MPa.

Evaporator with PVC plastic water board, corrosion resistance. Chilled water along the diaphragm up and down circuitous flow, in order to increase the spoiler effect to improve the evaporator heat transfer capacity.

Using the latest DAC corrugated spiral high efficiency heat transfer tubes, strengthen the fluorine side heat transfer capacity, improve the heat transfer coefficient to ensure that the unit good refrigeration and heating performance.

Electronic control

Air-cooled hot and cold water unit uses a microcomputer as the core of the control system, the control system control precision, anti-interference ability to ensure that the unit safe, reliable and economical operation.

Energy regulation automatic control can make the unit always in the best economic mode point efficient operation.

Protection
 function complete unit with overload, short circuit protection, frost protection, high and low voltage protection, overheating protection and other functions.


Technical Data
 
Model Unit 150 180 250 320 380 430 500
Cooling capacity * kW 156 180 250 320 380 428 497.6
Heating capacity * kW 180 198 276 353 416 474 550
Compressor
Qty Nr. 1 1 1 1 1 2 2
Cooling power input * kW 49.3 54.2 77.4 96.7 114 131.6 154.8
Cooling current * A 87.8 95.2 134 166 199 229.2 268
Heating power input * kW 48.4 53.2 76 95 112 129.2 152
Heating current * A 86.5 93.7 132 164 196 225.7 264
Energy adjustment steps step 4 4 4 4 4 8 8
Evaporator  
Water flow rate   m3/h 26.7 31 42.8 54.8 65 74 85.6
Water side pressure drop kPa 41 41 42 42 42 42 43
Water pipe  DN 100 100 100 125 125 125 125
Axial Fan
Fan motor number Nr. 4 4 6 6 8 10 12
Power input kW 4*2.2 4*2.2 6*2.2 6*2.2 8*2.2 10*2.2 12*2.2
Current input A 4*5.6 4*5.6 6*5.6 6*5.6 8*5.6 10*5.6 12*5.6
Air flow m3/h 68000 96000 144000 144000 196000 240000 288000
Dimensions
Length mm 2500 2500 3300 3590 4680 5800 6790
Width mm 2160 2160 2160 2160 2160 2160 2160
Height mm 2450 2450 2450 2450 2450 2450 2450
Sound pressure level ** dB(A) 73 73 75 75 78 80 81
Net weight kg 2050 2350 2750 3150 3650 4800 5250
 
Model Unit 570 640 700 760 870 930 1000 1180
Cooling capacity * kW 568 637.8 700 758 868 923.8 992.8 1172
Heating capacity * kW 630 706 772 827 953 1014 1086 1264
Compressor
Qty Nr. 2 2 2 2 3 3 3 3
Cooling power input * kW 174.1 193.4 210.7 228 268.8 286.4 309.6 348.2
Cooling current * A 300 332 365 398 467 497.2 536 600.4
Heating power input * kW 171 190 207 224 264 281.2 304 342
Heating current * A 296 328 360 392 460 489.7 528 591.2
Energy adjustment steps step 8 8 8 8 12 12 12 12
Evaporator  
Water flow rate   m3/h 97.4 109.7 120 130 149 159 170.8 201.6
Water side pressure drop kPa 43 44 45 45 45 45 45 45
Water pipe  DN 125 150 150 150 150 150 150 200
Axial Fan
Fan motor number Nr. 12 12 14 16 18 18 18 20
Power input kW 12*2.2 12*2.2 14*2.2 16*2.2 18*2.2 18*2.2 18*2.2 20*2.2
Current input A 12*5.6 12*5.6 14*5.6 16*5.6 18*5.6 18*5.6 18*5.6 20*5.6
Air flow m3/h 288000 288000 333600 384000 432000 432000 432000 576000
Dimensions
Length mm 6790 7190 8280 9370 10290 10580 10980 11780
Width mm 2160 2160 2160 2160 2160 2160 2160 2160
Height mm 2450 2450 2450 2450 2450 2450 2450 2450
Sound pressure level ** dB(A) 81 81 82 83 83 83 83 83
Net weight kg 5600 6150 6900 7600 8900 9650 10000 11000
 
* The performance values refer to the following conditions:
 
Cooling: ambient air temperature 35ºC; evaporator water in/out temperature 12/7ºC.
 
Heating: ambient air temperature DB 7ºC, WB 6ºC; condenser water in/out temperature 40/45ºC.

** Sound pressure measured at a distance of 1 m and a height of 1.5 m above the ground in a clear field.





 

Send your message to this supplier